Model |
3W3-10k 3W3-15k 3W3-20k 3W3-30k 3W3-40k |
Output capacity |
10KVA 15KVA 20KVA 30KVA 40KVA |
Input |
Voltage |
380VAC±20%(3φ+N)(at normal load) |
Frequency range |
45-65 Hz |
Power factor |
0.95 |
Output |
Voltage |
380 VAC 3φ+N |
Setting range |
346-415 VAC (on the control panel) |
Crest factor |
3:1 |
Wave form |
sinewave |
Distortion with liner load |
2.5% |
Stability voltage at steady state |
±1% |
Stability voltage at transient state |
±4% |
Frequency |
50/60 Hz the same of input |
Frequency stability with synchronization |
frequency is same as bypass |
Frequency stability without synchronization |
±0.05% |
Effective |
92% |
Overload |
110%/125%/150% nominal voltage 300/30/3 s |
Battery |
Type |
sealed lead-acid maintenance free |
VDC |
192+192 VDC / 288+288VDC | 288+288VDC |
Widing |
Different battery combinations |
Bypass |
Type |
STATIC+manual per maintenance operation |
Voltage |
380VAC±15%(±10%~±20%) 3Ø+N (on the control panel) |
Input frequency range
|
±2%(+1%~+5%)(on the control panel) |
Overload capacity per 1 min. |
200% |
Transfer time |
AC fault |
0ms |
UPS fault |
< 2ms |
System |
Remote signaling
|
3 tension f.e.contacts(mains failure,bypass,prealarm end discharge battery) |
Remote command |
EPO and Bypass |
Computer interface |
Standard RS232x2 |
Operating temperature |
0-40℃ |
Relative humidity |
95% without condensation |
Max operating altitude |
1000m at rated power An(-1% An for each 100m over i 1000m)-max 4000m |
Cooling |
force venational(fan speed fungating of load) |
Noise level at 1 m. dBA |
< 56dBA |
Protection level |
IP20 |
Applicable standards |
Safety EN50091-101,Electromagnetic compellability EMC EN 50091-2 liv.A |
Option
|
Insulation transforms-harmonic suppression filter-parallelism kit up to six units |
Dimensions(WxDxH) |
505x720x1135mm | 505x795x1210 mm |
Weight(UPS only) |
100kg 114kg 120kg 126kg 132kg |