SP6K~40K(Three in and single out)

Mode

SP6K

SP10K

SP15K

SP20K

SP30K

SP40K

Capacitg(KW)

6KVA/4.8

10KVA/8

15KVA/12

20KVA/16

30KVA/24

40KVA/32

Voltage

Three phase with four Lines+ground wire ,380V±25%

Noise

≤60dB(distance 1m)

≤65dB(distance 1m)

Size

620×343×995

650×700×1510

(W×D×Hmm)

Weight(Kg)

130

165

180

220

400

450

(excludingthebattery)

Common parameters

Input

Frequency

50Hz /60Hz ± 10%

Power actor

≥92%

Output

Voltage

{0>
110V± 0.5%<}0{><0}

Voltage regulation

Stable voltage±1%,dynamic oltage±2%,(0-100% load
fluctuation20ms)

Frequency stableness

50Hz /60Hz ± 0.5%

Frequency torsion rate

Less than 1Hz / second

Instant load status

± 0.4%(100% instant load fluctuation)

Harmonic distortion

For linear load, less than 3%(full load),total rectifying
harmonics islass than 5%

Overload capacitance

150%

Wave form

Sine wave

efficiency

Input AC to output AC

Above 90%

Transfer time

Mains power supply fails

or restores

0 second

Turns from UPS to BYPASS

Less than 4 ms

Battery

DC Voltage

192V

Charging time

After it is fully charged, it can be filled to 90% of the total
capacity after it is charged for 8 hours.

Warning sound

Battery discharge

If the main power fails, it buzzes once every 4 seconds.

If the battery is low, it buzzes once every 0.5 seconds.

If the battery stops discharging, it buzzes continuously.

In fault tatus

Continuously buzzes

 

Internal
Protecting

device
LCD

panel

 

 

 

 

Battery

Automatically shuts down the machine when the battery power is
low, it has no fuse switch protection.

Overload

After the overload (110~150%) lasts for 10 seconds,it automaticallyjumps
to BYPASS. It can automatically restore normal state.

Temperature is too high

If the internal temperature of the UPS>85°C, it will
automatically jump to BYPASS.

Output short circuit

Limits Current, automatically shuts down the machine, without
fuse switch protection.

UPS is abnormal

Automatically jumps to BYPASS mode and starts direct mains power supply.

Noise Filter<0}

10~10KHz at 40 db; 100KHz~100MHz at 70 db

LCD display

Indicating input and output voltage, frequency; battery voltage and output
power (%);Temperature

Battery BVL

One LED, it glows when the battery voltage is low.

Outside

environment

Temperature

0~40℃

Relative humidity

10%~90% (No condensation)

Operation condition

Lower than 1500 meters above sea level (altitude)